Reverse Osmosis (RO)

Home > Products > Reverse Osmosis (RO)

  • Reverse Osmosis Integrated System Single Pass/Double Pass

Reverse Osmosis Integrated System Single Pass/Double Pass

ROC-200 series reverse osmosis application control integrated system is in conformity with the needs of the integrated water treatment process control system transformation and upgrading. The system uses a 7-inch color touch screen as the main operating platform. Water quality measurement parameter collection, RO single/double process control process is highly integrated.

Share:

Product Description

Product Description

ROC-200 series reverse osmosis application control integrated system is in conformity with the needs of the integrated water treatment process control system transformation and upgrading. The system uses a 7-inch color touch screen as the main operating platform. Water quality measurement parameter collection, RO single/double process control process is highly integrated.

The controller integrates various detection methods such as RO system operation programs, DI/DO control, water quality, and flow detection. RO controllers are available all at once.

ROC-210 is a single-stage reverse osmosis application control integrated system, and the ROC-220 is a two-stage reverse osmosis application control integrated system that satisfies users' different process options. The flow meter and conductivity sensor configuration can be selected based on single and double stages

Feature

*Reverse osmosis measurement and control integrated machine, integrated measurement, process control, display function as one unit;

*7-inch Touch screen displays process flow and parameter settings;

*All-in-one integrated reverse osmosis automatic control function, no need to be equipped with PLC and other equipment;

*Human-machine interface combines measurement display, process parameter setting, consumable management, data query and other functions;

*Pane I mount, su i tab I e for sma I I and medium reverse osmosis systems;

*Can provide personalized and customized products according to customer processes and needs


Application

Applicable to a variety of small and medium-sized single-stage, two-stage reverse osmosis application control integrated system. Simple operation, complete measurement configuration, and highly integrated system.


Technical Parameter

ROC-210 Single Pass RO Control SystemsROC-220 Double Pass RO Control Systems
Measurement parameters:
Conductivity: Feed Water, Primary Produce WaterFeed Water, Primary Produce Water , Secondary Produce Conductivity
Flow Rate: Feed Flow, Primary Produce Flow, Primary Concentrated FlowFeed Flow, Primary Produce Flow, PrimaryConcentrated Flow ,Secondary Produce Flow
pH: NoPramary Produce pH
Measurement Range: 
onductivity: Feed Water: (0-2000) µSiem or (0-20000) µSiem; Primary Produce Water: (0-200 ) µSiem Secondary Produce Water: (0-20) µSiem pH: 0-14
Acquire the Signal:
1.Raw Water Low Pressure; 

2.Pramary boosterpump inlet Low-pressure;

3.Pramary booster pump outlet High-pressure;

4.Pramary produce tank high level;

5.Pramary produce tank low level; 

6.Preprocessing Signal.

1.Raw Water Low Pressure;

2.Pramary booster pump inlet Low-pressure; 

3.Pramary booster pump outlet High-pressure; 

4.Pramary produce tank high level;

5.Pramary produce tank low level;

6.Secondary Booster Pump Outlet High pressure;

7.Secondary Produce Tank Low Level; 

8.Secondary Produce Tank High Level; 

9.Preprocessing Signal

Control Output:

1.Inlet Valve;

2.Primary Flush Valve;

3.Primary Drain Valve;

4.Antiscalant pump;

5.Feed Pump;

6.Pramary booster pump

1.Inlet Valve;

2.Primary Flush Valve;

3.Primary Drain Valve;

4.Antiscalant pump;

5.Feed Pump;

6.Pramary booster pump

7. Secondary Booster Pump;

8.Secondary Flush Valve;

9. Secondary Drain Valve;

10.pH Acid-base adjustment pump

Contro I Power: DC24V士4V
Dimensions: (203*145*55) mm
lnstallation Size: (192*138)mm Panel flushbonading mounting 